RDHx Test Guide (Via Rack Mounted Air-Cooled Load Banks)
Posted by Vera Su on
1. Overview
Rear Door Heat Exchanger (RDHx) is an air-to-liquid cooling device mounted on the rear of server racks, designed to remove heat from high-density IT equipment (10–50 kW/rack). This guide focuses on via Rack Mounted air-cooled load banks to simulate traditional server heat loads, validating RDHx performance, airflow compatibility, and baseline cooling capability before/after liquid cooling deployment.
Air-cooled load banks dissipate heat via forced-air fans, replicating the hot exhaust of standard air-cooled servers—ideal for RDHx pre-installation baseline testing, airflow validation, and comparison with liquid-cooled performance.

2. Reference Standards & Scope
2.1 Industry Standards
- ASHRAE TC 9.9 (Data Center Cooling Standards)
- YD/T 4024-2022 (Data Center Liquid Cooling Technical Requirements)
- UL 62368-1 (Electrical Safety for Audio/Video, Information and Communication Technology Equipment)
- NFPA 110 (Emergency Power Systems)
2.2 Test Scope
- RDHx airflow resistance & heat dissipation efficiency
- Rack inlet/outlet temperature distribution
- HVAC compatibility & data center PUE baseline
- Structural integrity, safety, and alarm functionality
- Air-cooled vs. liquid-cooled performance comparison
3. Test Environment & Preparations
3.1 Environmental Conditions
- Ambient temperature: 22–26°C
- Relative humidity: 40%–60% (non-condensing)
- Atmospheric pressure: 86–106 kPa
- Temperature fluctuation: ≤±1°C
3.2 Air-Cooled Load Bank Specifications
- Power range: 10–50 kW (0–100% step adjustment)
- Voltage: 380V/400V 3-phase (50/60 Hz)
- Cooling method: Forced-air cooling (variable-speed fans)
- Airflow: 0.5–2.0 m³/s (per rack)
- Control: Local/remote monitoring (kW, temperature, airflow)
3.3 Instrumentation (Calibrated)
- Temperature sensors: ±0.1°C accuracy (inlet/outlet/ambient)
- Anemometer: ±2% FS (airflow velocity)
- Power analyzer: ±0.5% FS (kW, kVA, PF)
- Differential pressure gauge: ±1 Pa (cold/hot aisle pressure)
- IR camera: ±0.5°C (surface temperature distribution)

3.4 Pre-Test Checklist
- RDHx physical inspection: No damage, secure mounting, intact seals
- Load bank connection: Proper grounding, cable torque verified, no loose connections
- Safety: Fire extinguisher (Class C), PPE (insulated gloves, face shield), clear ventilation
- Liquid loop (if applicable): Isolation valves closed, no leakage, pressure 0.4–0.6 MPa
4. Core Test Items & Procedures
4.1 Baseline Air-Cooled Test (Without RDHx)
Objective: Establish baseline data for traditional air-cooled racks.
- Install air-cooled load banks in the test rack (no RDHx mounted)
- Set load bank to 10 kW/20 kW/30 kW/50 kW (steady state)
- Record data every 5 mins for 30 mins per load:
- Rack inlet temperature (cold aisle)
- Rack outlet temperature (hot aisle)
- Load bank airflow & power consumption
- Ambient temperature & humidity
- Cold/hot aisle differential pressure
- Calculate baseline metrics:
- Heat rejection to room: 100% of load bank power
- Average outlet temperature: ≤35°C (HVAC design target)
- Baseline PUE: Data center power / IT load
4.2 RDHx Airflow & Thermal Performance Test
Objective: Validate RDHx heat removal with air-cooled load bank simulation.
- Mount RDHx on the test rack rear; connect liquid loop (if open-loop test)
- Set load bank to target loads (10/20/30/50 kW); RDHx liquid supply: 22°C, 0.5 MPa
- Run steady state for 60 mins per load; record:
- RDHx inlet/outlet air temperature
- Liquid supply/return temperature & flow rate
- Heat removed by RDHx: Q = m × c × ΔT (liquid side)
- Residual heat to room: Load power – RDHx heat removal
- RDHx surface temperature (IR camera scan)
- Acceptance Criteria:
- RDHx heat removal ≥ 80% of load bank power (at 22°C supply)
- Rack outlet temperature ≤ 28°C (RDHx cooled)
- Surface temperature uniformity: ≤5°C (no hot spots)
4.3 Airflow Resistance Test
Objective: Measure RDHx impact on rack airflow.
- Set load bank to 30 kW (constant); adjust RDHx fan speed (if active) or liquid flow (if passive)
- Measure airflow at rack inlet/outlet with/without RDHx
- Calculate airflow resistance: ΔP = P_inlet – P_outlet
- Acceptance Criteria:
- Airflow reduction ≤ 10% vs. no RDHx
- ΔP ≤ 5 Pa (no excessive airflow restriction)
4.4 Transient Load Response Test
Objective: Verify RDHx performance under sudden load changes.
- Start load bank at 10 kW; ramp to 50 kW within 10s (step change)
- Record temperature, airflow, and liquid parameters every 1s for 5 mins
- Acceptance Criteria:
- RDHx stabilizes within 30s
- No over-temperature alarm (>30°C)
- Pressure fluctuation ≤ ±10%
4.5 Safety & Alarm Function Test
Objective: Validate RDHx safety mechanisms with air-cooled load banks.
- Over-temperature alarm: Simulate RDHx outlet air >30°C; verify alarm & load reduction
- Liquid leakage alarm: Simulate minor leak; verify detection & valve shutdown
- Power failure: Cut off RDHx power; verify load bank safety shutdown
- Acceptance Criteria: All alarms trigger correctly; no safety hazards
4.6 Long-Term Stability Test
Objective: Validate reliability under continuous operation.
- Set load bank to 80% rated power (40 kW); run for 500 hours
- Monitor parameters daily: Temperature, airflow, pressure, leakage
- Acceptance Criteria:
- No performance degradation (≤5% heat removal drop)
- No leakage or structural damage
- All components operate normally
5. Data Analysis & Reporting
5.1 Key Metrics to Report
- Baseline vs. RDHx-cooled outlet temperature
- RDHx heat removal efficiency (%)
- Airflow resistance (Pa)
- PUE reduction (baseline vs. RDHx)
- Temperature uniformity (°C)
- Transient response time (s)
5.2 Test Report Template
- Test Overview: Date, location, RDHx/load bank model, operator
- Environmental Conditions: Temp, humidity, pressure
- Test Data: Raw data tables, curves (temperature/time, airflow/load)
- Performance Analysis: Comparison with baseline & design specs
- Compliance: Pass/fail status for each test item
- Recommendations: Optimization for airflow, liquid parameters, or maintenance
6. Advantages of Air-Cooled Load Banks for RDHx Testing
- Cost-effective: No liquid loop required; easy deployment
- Realistic simulation: Replicates traditional server hot exhaust
- Baseline comparison: Enables direct air-cooled vs. liquid-cooled performance 对比
- Flexible testing: Suitable for pre-installation, on-site, and temporary test environments
7. Safety Precautions
- Always perform lockout/tagout (LOTO) during electrical connections
- Maintain a minimum 1m clearance around load banks for ventilation
- Avoid contact with hot surfaces (RDHx/load bank) during operation
- Stop the test immediately if abnormal noise, smoke, or leakage occurs